UL Certification |
File Nr. E502533 for category QEUY2/8 for use below 1000V |
|
File Nr. E502534 for category DLAR2/8 for use above 1000V |
Material |
Polyester material reinforced with fiberglass BMC RF 3/20 |
Operating Temperature |
°C: – 40° + 130° |
Fire reaction |
UL94-V0 File Nr. E205214 |
|
HL2 according to the EN45545-2 |
Thread Material |
Galvanized Steel |
H |
60 mm |
E |
M10: 16 mm / M12: 17 mm / M16: 22 mm |
Tightening Torque |
M10: 24 Nm / M12: 36 Nm / M16: 50 Nm |
Operating Voltage |
3000 V |
A.C. surface flashover voltage |
20 KV |
A.C. internal flashover voltage |
50 KV |
Tensile stress |
1.500 DN |
Cantilever stress |
600 DN |
Compressive stress |
10.000 DN |
Twisting stress |
8 DN x mm |
Package |
10 pcs |
Weight of package |
3,50 kgs |